Three-phase UPS from 60 to 200 kVA
This new generation of transformerless UPS solves all the major problems of IT managers and office managers. Cost reduction and 100% uptime are their top priorities. Multi Sentry provides the lowest cost of ownership of any UPS system, energy efficiency, scalable flexibility, high availability and easy maintenance.
Multi Sentry Characteristics:
MODELS | MST 60 | MST 80 | MST 100 | MST 125 | MST 160 | MST 200 |
INPUT | ||||||
Rated voltage (V) | 380 / 400 / 415 three-phase + N | |||||
Rated frequency (Hz) | 50 / 60 | |||||
Voltage tolerance | 400 ±20% @ full load1 | |||||
Frequency tolerance [Hz] | 40 – 72 | |||||
Power factor @ full load | 0.99 | |||||
Current distortion | THDI ≤3% | THDI ≤2.5% | ||||
BYPASS | ||||||
Rated voltage [V] | 380 / 400 / 415 three-phase + N | |||||
Number of phases | 3 + N | |||||
Voltage tolerance (Ph-N) [V] | 180 / 264 (selectable) | |||||
Rated frequency [Hz] | 50 or 60 (selectable) | |||||
Frequency tolerance | ±5% (selectable) | |||||
Bypass overload | 125% for 60 min., 150% for 10 min | |||||
OUTPUT | ||||||
Nominal power [kVA] | 60 | 80 | 100 | 125 | 160 | 200 |
Active power [kW] | 54 | 72 | 90 | 112.5 | 160 | 200 |
Power factor | 0.9 | 1 | ||||
Number of phases | 3 + N | |||||
Rated voltage [V] | 380 / 400 / 415 three-phase + N (selectable) | |||||
Static variation | ±1% | |||||
Dynamic variation | ±3% | |||||
Crest factor [lpeack/lrms] | 3:1 | |||||
Voltage distortion | ≤1% with linear load / ≤3% with non-linear load | |||||
Frequency [Hz] | 50 / 60 | |||||
Frequency stability during battery operation | 0.01% | |||||
BATTERIES | ||||||
Type | VRLA AGM/GEL/NiCd/Li-ion/Supercaps | |||||
Recharge time | 6 h | |||||
OVERALL SPECIFICATIONS | ||||||
Weight without batteries [kg] | 190 | 200 | 220 | 250 | 450 | 460 |
Dimensions (WxDxH) [mm] | 500x830x1600 | 650×830 x1600 | 840x1035x1900 | |||
Communications | 3 slots for communications interface / USB / RS232 | |||||
Ambient temperature for the UPS | 0 °C – +40 °C | |||||
Recommended temperature for battery life | +20 °C – +25 °C | |||||
Range of relative humidity | 5-95% non-condensing | |||||
Colour | Dark grey RAL 7016 | |||||
Noise level at 1 m [dBA±2] (SMART ACTIVE ) | <63 | <50 | ||||
IP rating | IP20 | |||||
SMART ACTIVE efficiency | up to 99% | |||||
Standards | European directives: L V 2014/35/EU low voltage Directive EMC 2014/30/EU electromagnetic compatibility Directive Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2; RoHS compliant Classification in accordance with IEC 62040-3 (Voltage Frequency Independent) VFI – SS – 111 | |||||
Moving the UPS | castors (60 – 200 kVA) | |||||
1 For wider tolerance conditions apply |
GP series batteries (12V, 33-200 Ah) provide long life and excellent discharge performance, ideal for UPS and inverter applications.
Diesel generator sets of FOX series with capacity from 9 to 20 kVA are designed for reliable backup and main power supply.