- Shelter cooling
- Modular data centers
- Direct Free Cooling
- For use in telecommunications, infrastructure
Benefits
- Innovative technology and high-quality components for low energy consumption
- Suitable for residential areas due to its low noise
- Plug and play and therefore immediately ready for connection and use
Technical Data
- Cooling capacity total (kW) 5 - 16
- Airflow volume (m3/h) 1,100 - 3,300
- Sizes 8
Features
- Factory tested, filled with refrigerant and ready for operation from the very first day
- Available with EC compressor
- Optionally with Free Cooling module
- Condensation pressure control
- Outside air conditions: -25/+50 °C winter/summer
- Automatic restart after power failure
- Filter monitor
- Easy installation and maintenance
- G3 air filter
- Refrigerant R407C
Control and monitoring
The C2020 consists of a controller and an optional operator terminal. The controller controls all the functions of the Split-Air-3 unit. The operator terminal, consisting of a keypad and LCD, displays the most important operating states and alerts.
Sequencing
- The C2020 enables up to ten units to be configured in a single air conditioning system. If an individual unit drops out or the heat load rises, the standby unit is switched in for additional support
- The operating times of all connected air conditioning units are compared to make sure each one is used to an equal extent
Night mode
- Time-controlled limitation of the condenser and evaporator fan speed for quiet operation
- Energy-saving mode
- The (adjustable) fan speed is automatically reduced at times when neither heating nor cooling is required
Monitoring and alarm relaying
- Via BMS systems (Modbus onboard, further protocols via WIB 1000)
- Nine potential free contacts are available: Alarms can be assigned a high or low priority
- Via GSM modem (CompTrol SMS)
Simple configuration and software updates
- Central configuration of units from a laptop
- Hardware key for uploading and downloading software without a laptop and/or copying the configuration onto other units
- High-pressure alarm management
- In order to avoid unnecessary service callouts, high-pressure alarms are initially reset three times automatically. Then, after the fourth error message, the alarm must be manually deleted after four hours
WIB 1000
WIB 1000 is the all-in-one interface for data exchange and monitoring
- Ongoing retrieval of data from the controller
- Ethernet interface
- Easy connection to existing building management system
- Simultaneous HTTP and SNMP
- Easy, fast configuration from a laptop
- Compatible with all common BMS systems
- Communication via SNMP and HTTP IP protocols