Technical Specifications - A Brief Overview

  • Classification IEC/EN 62040-3 VFI-SS-111
  • Operating mode On-line double conversion
  • Classification 60, 80, 100, 120 kW
  • Parallel operation 10 ИБП в параллель
  • Power range 60 кВт – 1200 kW
  • Output PF 1.0
  • Efficiency in on-line to 96 %
  • Efficiency in eco mode >99 %
  • Occupied space 0.3 m²
  • Specific power per m² 200 – 400 kW / m²
  • Weight without batteries 198 – 230 kg
  • Input THDI 3.5 %
  • Input (PF) 0.99
  • Reverse Current Protection Option
  • Internal technical bypass Yes


Unsurpassed Power Performance
Key Features:

  • High reliability and availability with True on-line double conversion (VFI)
  • Minimal energy loss in on-line efficiency mode up to 96% and 99% in ECO mode
  • Optimized for modern IT loads. Nominal output PF = 1.0
  • Low input distortion; at the input PF = 0.99 @ 100% load - ITHD ≤ 3.5%
  • Up to 10 UPSs can be connected in parallel to reserve and / or increase the total output power.
  • “All inclusive” with internal technical bypass and reverse current protection
  • No surprises in case of network failures - manual and automatic battery test provides information on the status of the batteries at any time
  • Front access and low time MTTR ensures low downtime during planned and unscheduled work
  • Easy to use and monitor